CATV Flooded Batteries
"Voltex Cable TV Batteries
deliver plenty of power for longer reliable life."
Discharge
Performance Amps | Discharge
Performance Watts
| Part No: |
Cells |
Voltage |
Approx. Weight |
Electrolyte |
Max. Discharge
Current |
Watts Avail.
1 min. watts
to 1.50 VPC |
Milliohms
Resistance
Full Charge |
| CATV-31 |
6 |
12.6 |
59.5 |
Flooded |
960 Amps |
7325 |
3.0 |
Discharge
Performance Watts
Constant Power per battery @ 77 Deg.F (25 Deg.C)
(Operating Time to End Point Voltage)
End Point
Volts Per Cell |
5 Min. |
10 Min. |
15 Min. |
20 Min. |
30 Min. |
40 Min. |
50 Min. |
| 1.75 |
3105 |
2235 |
1775 |
1480 |
1120 |
900 |
753 |
| 1.70 |
3300 |
2340 |
1845 |
1535 |
1155 |
928 |
776 |
| 1.67 |
3370 |
2370 |
1860 |
1545 |
1160 |
931 |
778 |
| 1.60 |
3535 |
2435 |
1895 |
1565 |
1170 |
938 |
784 |
| 1.55 |
3610 |
2460 |
1910 |
1575 |
1180 |
947 |
793 |
Back to Top
Discharge
Performance Amps
Constant Current Amperes @ 77 Deg.F (25 Deg.C)
(Operating Time to End Point Voltage)
End
Point
Voltage
|
60 Min. |
3 Hrs. |
5 Hrs. |
6 Hrs. |
8 Hrs. |
10 Hrs. |
12 Hrs. |
20 Hrs. |
24 Hrs. |
48 Hrs. |
| 1.90 |
48.4 |
21.5 |
14.3 |
12.3 |
9.69 |
8.00 |
6.83 |
4.33 |
3.66 |
1.89 |
| 1.85 |
54.6 |
23.6 |
15.6 |
13.4 |
10.5 |
8.63 |
7.35 |
4.64 |
3.92 |
2.02 |
| 1.80 |
58.3 |
24.5 |
16.1 |
13.8 |
10.7 |
8.81 |
7.49 |
4.71 |
3.98 |
2.05 |
| 1.75 |
61.9 |
25.4 |
16.5 |
14.1 |
10.9 |
8.98 |
7.62 |
4.78 |
4.03 |
2.08 |
Back to Top |